#Sales Offer!| Get upto 25% Off:

Design a vertical turbine flocculator to treat 75,700 m3/d of water per day at a detention time of 30 minutes. Use three parallel treatment trains with four compartments per train. The temperature of the water is 20∘C, resulting in values of 1.002 × 10−3 kg/(m⋅s) and 998.2 kg/m3 for and ρ, respectively. The impeller diameter (D) to effective tank diameter (Te) ratio is 0.4. Assume a power number (Np) of 0.25 for a three pitch blade with camber, and a mean velocity gradient of 70s−1. Determine the following:

a. Dimensions of each compartment assuming they are cubes (m).

b. Impeller diameter (m).

c. Power input per compartment (W).

d. Rotational speed of each turbine (rpm).

Found something interesting ?

• On-time delivery guarantee
• PhD-level professional writers
• Free Plagiarism Report

• 100% money-back guarantee
• Absolute Privacy & Confidentiality
• High Quality custom-written papers

Related Model Questions

Feel free to peruse our college and university model questions. If any our our assignment tasks interests you, click to place your order. Every paper is written by our professional essay writers from scratch to avoid plagiarism. We guarantee highest quality of work besides delivering your paper on time.

Grab your Discount!

25% Coupon Code: SAVE25
get 25% !!